Description
Introduction
Schischek RedMax-50.75-S | explosion-proof ¼-turn actuator, Open-close / 3-position, 50/75 Nm. First and foremost, this actuator delivers 50/75 Nm torque and a universal 24…240 V AC/DC supply. In addition, you can flexibly choose Open-close / 3-position control, allowing you to easily use existing control systems. This increases operational reliability while the compact housing saves installation space.
Key features
- Explosion-proof actuator for zone 2/22, designed for HVAC and process rooms.
- Universal 24…240 V AC/DC supply; easy to integrate into existing systems.
- High torque in a compact form factor; saves installation space.
- 95° travel with ~5° pre-position for reliable valve or damper actuation.
- Brushless motor and 100% overload protection; long service life.
Technical specifications
| Series / size | RedMax, size M |
| Torque | 50/75 Nm |
| Supply voltage | 24…240 V AC/DC (self-adjusting) |
| Control | Open-close / 3-position |
| Feedback | 2 auxiliary switches |
| Spring return (fail‑safe) | No |
| Rotation angle | 95° incl. ~5° pre-position |
| Protection rating | IP67 (size M) |
| Explosion-proof | ATEX zone 2/22 |
| Operating environment | −40…+40 °C (T6) / −40…+50 °C (T5) |
| Housing | Coated aluminium (option: stainless steel or seawater-resistant) |
| Shaft connection | Double square 16 × 16 mm (size M) |
| Manual operation | Included (hexagon) |
| Heating | Integrated heating down to −40 °C |
| Auxiliary switches | 2 auxiliary switches |
| Ex safety circuit | No |
| Weight | ~9,5 kg (aluminium) |
Available variants
| Article name | Description | SKU |
| RedMax-50.75 | Electric, explosion-proof ¼-turn actuator, Open-close/3-position, 24…240 V AC/DC, 95° | RedMax-50.75 |
| RedMax-100 | Electric, explosion-proof ¼-turn actuator, Open-close/3-position, 24…240 V AC/DC, 95° | RedMax-100 |
| RedMax-150 | Electric, explosion-proof ¼-turn actuator, Open-close/3-position, 24…240 V AC/DC, 95° | RedMax-150 |
| RedMax-50.75-S | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with 2 auxiliary switches, 24…240 V AC/DC, 95° | RedMax-50.75-S |
| RedMax-100-S | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with 2 auxiliary switches, 24…240 V AC/DC, 95° | RedMax-100-S |
| RedMax-150-S | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with 2 auxiliary switches, 24…240 V AC/DC, 95° | RedMax-150-S |
| RedMax-30-F | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with spring return (~20 s), 24…240 V AC/DC, 95° | RedMax-30-F |
| RedMax-50-F | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with spring return (~20 s), 24…240 V AC/DC, 95° | RedMax-50-F |
| RedMax-60-F | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with spring return (~20 s), 24…240 V AC/DC, 95° | RedMax-60-F |
| RedMax-30-SF | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with spring return (~20 s), 24…240 V AC/DC, 95° | RedMax-30-SF |
| RedMax-50-SF | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with spring return (~20 s), 24…240 V AC/DC, 95° | RedMax-50-SF |
| RedMax-60-SF | Electric, explosion-proof ¼-turn actuator, Open-close/3-position with spring return (~20 s), 24…240 V AC/DC, 95° | RedMax-60-SF |
Application and installation
For example on butterfly valves, ball valves and safety valves. Because the actuator has a double square drive, you couple directly to the shaft. Manual operation is also provided for service. Note: in Ex-zones always use an Ex junction box and comply with local standards.
FAQ
Is this actuator suitable for my application?
Yes, compared to alternatives the RedMax-50.75-S covers both valves and dampers thanks to its 95° travel and the specified torque.
How fast does the spring return respond?
Not applicable
What feedback do I get?
2 auxiliary switches.
Do I need an Ex junction box?
Yes, unlike safe zones, in zone 2/22 you must use an Ex junction box (for example RedBox) for wiring.