Description
Combined duct Sensor for relative humidity and temperature – KFFT/R-xxx-I/SD
For measuring relative humidity and temperature in ducts or in rooms with increased protection requirements. The transmitter records the temperature and rel. humidity via an internal Sensor and converts it into a standardized analog output signal 0-10V or 4-20mA. Overview of humidity sensors
Technical data
Supply voltage at 0-10 V:15…36 V/DC, 24 V/AC Supply voltage at 4…20mA:15…36 V/DC Humidity Sensor element:capacitive Sensor Temperature Sensor element:capacitive Sensor Temperature Sensor element with passive temperature output:according to customer requirements Humidity measuring range:0…100% r. H. Humidity output: 0…10V or 4…20mA Humidity tolerance at 35%…70% r. H.:± 2% (25…90% r.H.) Temperature measuring range: -30°C … +70°C Temperature output with active version: 0…10V or 4…20mA Temperature tolerance: ± 0,5K analog output load 0-10V:10…100 kOhm analog output load 4…20mA:300…1000 Ohm Operating temperature:-30°C … +70°C Operating range:0…98% r. H. Response time r. H.:8 sec (63% dew point) Sensor tube (W x L):12 x 75 mm made of VA Connection:screw terminals 1.5 mm² Housing:Material PA6 15% GK, color RAL9010 Housing dimensions (L x W x H ) :75 x 69 x 44 mm Protection class:IP65 Sensor protection:Sintered filter made of HD polyethylene