Description
Room combination Sensor for relative humidity and temperature – RFFT/RI/S
For measuring relative humidity and temperature in residential and office buildings. The transmitter records temperature and relative humidity via an internal Sensor and converts them into a standardized analog output signal 0-10V or 4-20mA.
Technical data
Supply voltage at 0-10 V:15….36 V/DC, 24 V/AC Supply voltage at 4…20mA:15…36 V/DC Humidity Sensor element:capacitive Sensor Temperature Sensor element:capacitive Sensor Temperature Sensor element with passive temperature output:according to customer requirements Measuring range Humidity: 0…100% rel. hum. Humidity output: 0…10V or 4…20mA Humidity tolerance at 35%…70% rel. hum.:± 2% (25…90% rel.h.) Temperature measuring range: -30°C … +50°C Temperature output with active version: 0…10V or 4…20mA Temperature tolerance: ± 0,5K analog output load 0-10V:10…100 kOhm analog output load 4…20mA:300…1000 Ohm Operating temperature:-30°C … +50°C Operating range:0…98% rel. hum. Response time rel. hum.:8 sec (63% tau) Connection:screw terminals 1.5 mm² Housing:Material ABS, color RAL9010 Housing dimensions (L x W xH):87,5 x 87,5 x 30 mm Protection class:IP20