Description
Room controller temperature | RS485 Modbus | Indoor climate control, Measured values
Room controller temperature
Room controller temperature | RS485 Modbus | Indoor climate control, Measured values
| Toepassing type | Room controller |
|---|---|
| Doel | Space climate control, Measurement values |
| Meetwaarden | temperature |
| Interface | RS485 Modbus |
| Configuratie | BUS, DIP-schakelaars |
| Netwerktechnologie | RS485 Modbus |
| Gegevensoverdracht | RTU, half-duplex, baud rate 9,600, 19,200, 38,400 or 57,600, parity: none (2 stop bits), even or odd (1 stop bit) |
| Werkingsbereik temepratuur | -35..+70 |
| Uitgang spanning | 0..10 V, min. load 10 kΩ, cooling |
| Werkingsbereik vochtigheid | max. 85% RH without condensation |
| Nauwkeurigheid temperatuur | ±0.5 K (typ. at 21 °C) |
| Stroomvoorziening | 15..24 V = (±10%) SELV, 24 V AC (±10%) SELV |
| Energieverbruik | typ. 0.4 W (24 V =), 0.6 VA (24 V ~) |
| Toon | LED voor status feedback, green |
| Huisvesting | PC |
| Kleur | pure white |
| Beschermingsklasse | IP30, according to DIN EN 60529 |
| Aansluiting | screw terminal, max. 1.5 mm², cable entry via rear opening, predetermined breaking point (bottom and top) |
| Verpakkingslengte (mm) | 90 |
| Breedte van de verpakking (mm) | 90 |
| Verpakkingshoogte (mm) | 35 |
| Verpakking | 2x vouwkarton |
| Apparaatlengte (mm) | 85 |
| Breedte van het apparaat (mm) | 85 |
| Control | Modbus RTU |
| Sensor type | Active |
| Hoogte van het apparaat (mm) | 60 |
| Output | RS485 Modbus |
| Montage | installation on standard EU flush-mounted box (Ø=60 mm), mounted flush on the surface using screws, or with surface-mounted frame (see accessories), the base part can be mounted and wired separately |
| Communication | Modbus |
| Gewicht (g) | 50 |
| Uitgang schakelcontact | 1x triac output, heating, max. load 3 A, for 24 V ~, potential-free |
| Functies | temperature control, heating relay, cooling 0..10 V, integrated controller, presence |
| Werkende functies | adjustment of the setpoint temperature, occupancy detection, status displays |
| Bedieningselementen | potentiometer (P), labeling {[thermometer] – [scale] 0 [scale] +}, button (T) |
| Ingang | 2x input for potential-free contact |